Note 10: Senior Watch
The Senior Watch attribute may only be used with Burglar, Critical Condition Monitor, Universal, and Universal Logged zones. It is ignored
for all other zone types.
If a Burglar zone has Senior Watch enabled, then the Senior Watch only applies when the zone is disarmed and not bypassed. Whenever the
zone is violated, disarmed or unbypassed, the zone’s Senior Watch timer is reset to the programmed time. If that timer expires and the zone
is disarmed and not bypassed, then a Senior Watch Trouble event is posted for the zone to be reported. The trouble condition is not displayed
on the keypad and it does not prevent the area from being armed. A Senior Watch Trouble Restore event is posted for the zone to be reported
if the zone is then either violated, armed, or bypassed.
If a Critical Condition Monitor, Universal, or Universal Logged zone has Senior Watch enabled, then the Senior Watch only applies when the
zone is not bypassed. When the zone is violated or unbypassed, the zone’s Senior Watch timer is reset to the programmed time. If that timer
expires and the zone is not bypassed, then a Senior Watch Trouble event is posted for the zone to be reported. The trouble condition is not
displayed on the keypad. A Senior Watch Trouble restore event is posted for the zone to be reported if the zone is either violated or bypassed.
While a zone has a Senior Watch Trouble condition, its corresponding Senior Watch signaling device (programmable output) will stay ON
steady.
Note 11: The Listen-In Module
The Listen-In Module must be wired to the telephone lines in series with and behind the control panel. The Listen-In Module must be
connected to the panel as follows. A Line-Seized indicator line must be connected from the ACTIVE output on the Listen-In Module to an
assigned Listen-In Module zone on the panel. A Listen-In output line must be connected from an assigned output on the panel to the
ACTIVATE input on the Listen-In Module.
The zone programmed as the Listen-In Module zone is area independent and is used by the panel to determine whether or not the Listen-In
Module has seized the telephone line and has the microphone(s) active. The output programmed as the Listen-In Output may be assigned to
any combination of areas. It is used by the panel to signal the Listen-In Module for activation.
The Listen-In Module may be configured in one of two modes, Instant Seize mode or Answer mode.
If the Listen-In Module is configured in Instant Seize mode, then when it is first signaled from the panel, it instantly seizes the phone line and
signals the panel through the Listen-In Module zone but does not turn on the microphones. When the panel releases the connection to the
Central Station and deactivates the Listen-In Output, the Listen-In Module already has the line seized and assumes the connection.
If the Listen-In Module is configured in Answer mode, then after the panel has signaled it by activating and later deactivating the Listen-In
Output, the Listen-In Module starts its incoming call timer. The incoming call timer starts when the Listen-In Output is dactivated and runs
for five minutes. If a call comes in while the timer is running, then the Listen-In Module answers the call on the first ring. At that time, it
signals the panel through the Listen-In Module zone that it has seized the line.
When the control panel detects the Line-Seized signal from the Listen-In Module zone, it temporarily silences all alarm tones at the Control
Stations and the Bell Outputs, although the alarm output timers continue. When the Listen-In Module releases the phone line, it removes the
Line-Seized signal to the panel. When the control panel detects the Line-Seized signal has been removed, it no longer silences alarm tones at
the Control Stations and Bell Outputs. The Bell Outputs are reactivated if they have not timed-out.
Also, when the panel detects the Line-Seized signal from the Listen-In Module zone and gets an event (any event) to report to the Central
Station, the panel signals the Listen-In operator by momentarily seizing the phone line and producing a tone. This interrupts the Listen-In
Module connection for about one second but it does not hang-up the phone line. The panel also starts a two minute timer. It will not try to call
out to the Central Station until either the Line-Seized signal from the Listen-In zone is removed or the two minute timer expires, whichever
comes first. If the timer expires before the Line-Seized signal is removed, the panel seizes the line to dial out to the Central Station,
disconnecting and hanging up the Listen-In Module’s connection.
If an alarm is silenced through a Control Station during a Listen-In session, it has no impact on the Listen-In operation.
NOTE
If a Holdup Alarm event is reported to the Central Station, it is the Listen-In operator’s responsi-
bility to NOT activate the speakers on the Listen-In Module.